30 Amp Wire Size — NEC Guide for Copper & Aluminum

The NEC answer for 30-amp circuits: #10 AWG copper or #8 AWG aluminum at the 75°C column of NEC Table 310.15(B)(16). This guide explains why, shows common 30A applications, and includes voltage drop guidance for longer runs. Use the calculator below to verify the wire size and voltage drop for your specific circuit length.

30 Amp Wire Size — Quick Reference

Copper (75°C) #10 AWG — 35A rated
Aluminum (75°C) #8 AWG — 40A rated
Standard Breaker Size 30A (NEC 240.6)
NEC Source Table 310.15(B)(16)

Need to account for voltage drop on a longer run?

Calculate for Your Circuit Length →

Why #10 AWG Copper for a 30-Amp Circuit?

Per NEC Table 310.15(B)(16), #10 AWG copper is rated for 30A at 60°C and 35A at 75°C. Most residential and commercial panels and devices use 75°C-rated terminals, so #10 AWG copper satisfies a 30A overcurrent device at standard installation conditions.

The NEC requires that conductors be protected at their ampacity. Since #10 AWG copper is rated 35A at 75°C, pairing it with a 30A breaker is code-compliant — the breaker will trip before the wire overheats.

For aluminum, #8 AWG is the minimum: #8 AWG aluminum is rated 40A at 75°C, which is the next standard size up and satisfies protection by a 30A breaker with ampacity to spare.

Common 30-Amp Circuit Applications

  • Electric dryer: Standard residential dryer circuit — 240V, 30A double-pole breaker, NEMA 14-30 outlet, 4-wire required for new installs (NEC 250.140)
  • Air conditioner / heat pump (smaller units): Many window or mini-split A/C units rated ≤ 30A MCA
  • Welding outlet (small welder): 240V/30A NEMA 6-30 outlet for home shop welders
  • RV pedestal (30A): 120V single-pole NEMA TT-30 for RV hookups
  • Small subpanel feeder: 30A feeder to a small shed or workshop panel
  • Electric water heater: Some smaller tankless or storage units use a 30A circuit

Voltage Drop on 30-Amp Circuits

For a 240V, 30A circuit with #10 AWG copper, the voltage drop stays within the NEC 3% recommendation for runs up to approximately 75–80 feet (one-way). Beyond that, upgrade to #8 AWG copper to keep drop under 3%.

For 120V applications at 30A (uncommon but used for RV pedestals), #10 AWG copper is limited to approximately 35–40 feet before exceeding 3% voltage drop. Use the Wire Size Calculator to verify for your specific run.

#10 Cu, 240V, 30A — 3% drop limit ~78 ft (one-way)
#8 Cu, 240V, 30A — 3% drop limit ~124 ft (one-way)

Important Note on Dryer Wiring

NEC 250.140 (amended in the 1996 NEC) requires 4-wire connections (two hots, neutral, and ground) for new dryer circuits. Older homes may have 3-wire dryer circuits (two hots and neutral, with neutral doubling as ground) — this is permitted as a grandfathered installation but not allowed for new work or when replacing a receptacle.

When roughing in a new dryer circuit, always install 4-wire cable (10/3 with ground) or 4 individual conductors in conduit and a NEMA 14-30 outlet.

Frequently Asked Questions

Per NEC Table 310.15(B)(16): #10 AWG copper (35A at 75°C) or #8 AWG aluminum (40A at 75°C) are the minimum sizes for a 30A circuit at standard installation conditions.

A 30-amp double-pole breaker for 240V circuits (dryers, A/C, welders). A 30A single-pole breaker for 120V circuits (RV outlets). Both are standard NEC 240.6(A) sizes.

No. #12 AWG copper is rated 20A at 75°C. Using it with a 30A breaker violates NEC 240.4 by allowing more current than the conductor is rated for. Minimum is #10 AWG copper for a 30A circuit.

#10 AWG copper (4-wire: two hots, neutral, ground) with a 30A double-pole breaker and NEMA 14-30 outlet. NEC 250.140 requires 4-wire for all new dryer circuits.

Approximately 75–80 feet one-way before exceeding the NEC 3% voltage drop recommendation. For longer runs, upsize to #8 AWG copper (approximately 124 feet) to stay within 3%.

For 240V circuits, yes — a double-pole breaker is required to interrupt both hot conductors. For 120V applications at 30A (such as an RV outlet), a single-pole 30A breaker is used.