Circuit Details
Results
Minimum EGC per NEC Table 250.122. If conductors are upsized for voltage drop, EGC must also increase per NEC 250.122(B). Verify against current code and local amendments.
How to Use This Ground Wire Size Calculator
Select the rating of the overcurrent protective device (OCPD) protecting the circuit, and choose copper or aluminum for the EGC material. The calculator looks up the NEC Table 250.122 row for that OCPD rating and returns the minimum required AWG. This is the absolute minimum — if phase conductors are upsized for voltage drop, increase the EGC proportionally per NEC 250.122(B).
Why Ground Wire Size Matters
An undersized EGC may not carry enough fault current to clear the overcurrent device quickly, leaving equipment energized at a dangerous voltage. The NEC Table 250.122 minimums ensure the EGC can handle the worst-case fault current for the associated OCPD.
EGC sizing is frequently underspecified on subpanel feeders and service entrances — where the phase conductors get attention but the grounding means does not.
What Affects EGC Size
The OCPD rating is the primary driver. Conductor material matters because aluminum has higher resistance, requiring a larger AWG for equivalent fault-current capacity. If phase conductors are upsized beyond the NEC table minimum (for voltage drop, derating, or other reasons), the EGC must also be increased proportionally per NEC 250.122(B).
Common Ground Wire Sizing Scenarios
- Sizing the EGC for a 20-amp kitchen or bathroom circuit (#12 AWG copper minimum)
- Finding the EGC for a 100-amp subpanel feeder (#8 AWG copper minimum)
- Sizing an aluminum EGC for a 200-amp service entrance (#4/0 AWG aluminum)
- Checking whether an existing EGC must increase after upsizing circuit conductors for voltage drop
- Finding the correct ground wire gauge for a 60-amp EV charger or HVAC circuit
Frequently Asked Questions
NEC Table 250.122 determines the minimum EGC size based on the overcurrent device protecting the circuit, for both copper and aluminum conductors.
An EGC connects the metal parts of equipment not normally carrying current back to the grounding system, providing a fault current return path so overcurrent devices can clear ground faults quickly.
Per NEC Table 250.122, a 20-amp OCPD requires a minimum #12 AWG copper or #10 AWG aluminum EGC.
Per NEC Table 250.122, a 100-amp overcurrent device requires a minimum #8 AWG copper or #6 AWG aluminum equipment grounding conductor.
Aluminum EGCs are permitted by NEC 250.122 but must be larger than copper equivalents. Aluminum cannot contact earth or concrete, and terminations must be rated for aluminum conductor use.
Yes. Per NEC 250.122(B), when circuit conductors are increased in size beyond the NEC table minimum, the EGC must be proportionally increased using the ratio of the new conductor circular mil area to the original table-minimum area.